The figures follow ISO 13849-1 (Annex A risk graph, Annex F common-cause-failure scoring, simplified PL chart) cross-checked against several public sources, with SIL comparison from IEC 62061. The actual project must follow the standard edition you adopt and the machine-specific risk assessment; this article gives methods, parameter bands and lookup tables, not a compliance assessment.
40.1 Two letters first: PL is what you achieve, PLr is what you need
Every argument starts here:
- PL (Performance Level): the level a safety function actually achieves, calculated from architecture and reliability parameters, graded a to e.
- PLr (required Performance Level): the level the risk assessment demands, derived from severity, exposure and possibility of avoidance, also graded a to e.
There is only one acceptance condition: PL must be at least PLr. A function with PLr d may be built to PL d or PL e, but not PL c. One machine usually has several PLr values at once: a guard interlock may need PL d while speed monitoring in setup mode needs only PL c. PLr is defined per safety function, not as one number for the whole machine. Where a machine-specific type-C standard prescribes PLr directly, that value takes precedence.
Each PL corresponds to a band of average probability of dangerous failure per hour (PFH_D), evaluated over a 20-year mission time:
| PL | PFH_D (dangerous failures per hour) | Rough SIL counterpart |
|---|---|---|
| a | >= 10^-5 to < 10^-4 | none |
| b | >= 3×10^-6 to < 10^-5 | SIL 1 |
| c | >= 10^-6 to < 3×10^-6 | SIL 1 |
| d | >= 10^-7 to < 10^-6 | SIL 2 |
| e | >= 10^-8 to < 10^-7 | SIL 3 |
40.2 Step one PLr: the S x F x P risk graph, eight combinations
PLr comes from the risk graph in Annex A of ISO 13849-1, built from three parameters:
- S (severity): S1 is slight, normally reversible injury; S2 is serious, normally irreversible injury, including death.
- F (frequency and duration of exposure): F1 is seldom or short exposure (rule of thumb: entering the danger zone less often than once every 15 minutes); F2 is frequent to continuous exposure.
- P (possibility of avoiding the hazard): P1 means avoidance is possible under specific conditions; P2 means avoidance is scarcely possible.
The three parameters give eight combinations (this table is consistent across the sources checked):
| S | F | P | PLr |
|---|---|---|---|
| S1 | F1 | P1 | a |
| S1 | F1 | P2 | b |
| S1 | F2 | P1 | b |
| S1 | F2 | P2 | c |
| S2 | F1 | P1 | c |
| S2 | F1 | P2 | d |
| S2 | F2 | P1 | d |
| S2 | F2 | P2 | e |
A widely circulated shop-floor checklist lists S2+F1+P2 as PLr c. That is wrong – the Annex A risk graph puts S2+F1+P2 at d (the neighbouring cells S2+F2+P1 and S2+F1+P2 are d and d respectively; do not copy this cell one level low). Getting this one cell wrong sets the whole safety function’s target one level too low.
The 2023 edition adds finer guidance on choosing P1 versus P2, considering the speed of hazard development, escape space, operator experience and supervision. You cannot simply relabel P2 as P1 to drop PLr from e to d – an assessor will ask you to defend it.

40.3 Step two Category: architectures B, 1, 2, 3, 4 and single-fault behaviour
Category describes structure and behaviour on fault; it is not itself a PL. The five designated architectures differ like this:
| Category | Structure | On a single fault | Typical implementation |
|---|---|---|---|
| B | Single channel | The safety function may be lost | Basic design and component selection only |
| 1 | Single channel | May still be lost, but a well-tried component and principle make it less likely | Proven safety relay with positively driven contacts |
| 2 | Single channel plus test channel | A fault between tests may be lost | Periodic testing, test rate at least 100 times the demand rate |
| 3 | Two-channel redundancy | A single fault does not lose the function and is detected where reasonably practicable | Dual channel plus diagnostics plus CCF measures; accumulated undetected faults can still lose it |
| 4 | Two-channel redundancy, high diagnostics | Single fault detected in time; accumulated faults must not lose the function | Dual channel plus DC >= 99% plus CCF; the route to PL e |
The 2023 edition tightens several rules: Category 2 requires at least low diagnostic coverage (>= 60%) in each part (input, logic, output), with a test rate at least 100 times the demand rate or a test at the moment of demand; complex components such as microcontrollers never count as well-tried; and PL e may not rely solely on fault exclusion.

40.4 Step three component inputs: MTTFd three bands, DCavg four bands, CCF >= 65
With the architecture set, fill in three parameters.
MTTFd (mean time to dangerous failure) – assessed per channel, in three bands:
| Band | Range |
|---|---|
| Low | 3 years <= MTTFd < 10 years |
| Medium | 10 years <= MTTFd < 30 years |
| High | 30 years <= MTTFd <= 100 years |
Each channel is capped at 100 years; you cannot buy a higher PL by quoting a reliability figure nobody can support. For electromechanical parts (contactors, switches), use the manufacturer’s B10d and the number of operations per year n_op: MTTFd = B10d / (0.1 x n_op). T10d = B10d / n_op sets the preventive replacement interval. A door switch opened a few times a day and one opened every 30 seconds may both be “high” MTTFd, but the second has a T10d of only a few years and must be scheduled for replacement.
DCavg (average diagnostic coverage) – four bands: none (<60%), low (60-90%), medium (90-99%), high (>=99%). Typical measures: test-pulse cross-monitoring of dual-channel inputs up to 99%, positively driven NC+NO auxiliary contact monitoring up to 99%, EDM feedback around output contactors about 90-99%, single channel with no monitoring = 0%. DCavg is the dangerous-failure-weighted average across subsystems; tools such as SISTEMA and PAScal compute it from a bill of materials.
CCF (common cause failure) – scored with the Annex F checklist out of 100; Categories 2, 3 and 4 require at least 65 points. Typical scored measures: physical separation of channels (up to about 15 points), diversity using different technologies or manufacturers (up to about 20 points), protection against over-voltage, over-current and over-temperature, designer competence and training, and environmental control (temperature, humidity, vibration, EMC). Two channels on the same PCB and the same 24 V supply can fail together from one short circuit – no amount of redundancy helps.

40.5 Step four look up PL from Category x DCavg x MTTFd, then verify PL >= PLr
Put the results into the simplified PL chart (the table below is consistent across the sources checked):
| Category / DCavg | MTTFd low | MTTFd medium | MTTFd high |
|---|---|---|---|
| B / none | a | b | – |
| 1 / none | – | – | c |
| 2 / low | a | b | c |
| 2 / medium | b | c | d |
| 3 / low | b | c | d |
| 3 / medium | c | d | d |
| 4 / high | – | – | e |
Compare the resulting PL with PLr from step one: only PL >= PLr passes. A safety function is a series chain of input (sensor), logic (safety relay or safety PLC) and output (contactor or drive), and the total PL is limited by the weakest subsystem; summing the PFH_D values of the parts gives the total PFH_D.
Two cautions: different editions (2006, 2015, 2023) change chart boundaries and limiting conditions, so use the original chart from the edition adopted for the project; and this simplified table only gives band-level lookup. To claim PL e or to build a full argument, use a tool such as SISTEMA for a complete PFH_D calculation.

40.6 Three upgrade paths when PL falls short
When PL < PLr, take these routes from cheapest to most effective:
- Change the architecture: move from a single channel to dual channel (Category 2 to 3/4). This is the most effective step, but CCF separation must come with it.
- Use higher-MTTFd components: replace a low-band door switch or contactor with one whose datasheet gives B10d and a high-band MTTFd, or reduce the operating frequency so T10d grows.
- Improve CCF and diagnostics: separate channel routing, over-voltage/current protection, add EDM readback and test pulses, lift the CCF score past 65 and move DCavg up a band.
If all three fail, go back to the risk assessment – check whether PLr was set too high (can the P2 judgement be defended?) instead of forcing the calculation to fit.
40.7 Two recurring traps: a PL e relay does not make a PL e machine; CE/UL is not a substitute
Trap one: a relay marked PL e means the machine is PL e. It does not. PL belongs to the whole safety function. A Category 3 dual-channel arrangement can land anywhere from b to e depending on MTTFd and DCavg – the same Category means different results with different component data and diagnostics. A weak door switch, logic unit or output contactor drags the whole chain down to the weakest link.
Trap two: a CE or UL mark, or a routine electrical safety test, removes the need for a PL assessment. It does not. CE marking is a regulatory conformity declaration and UL is a product safety certification; neither replaces the ISO 13849-1 PL assessment of a safety function, and a correct PL calculation does not waive other regulatory duties. They run in parallel.
40.8 Relationship to SIL: PL a-e and SIL 1-3
IEC 62061 grades safety functions with SIL, running in parallel with PL: PL a has no SIL counterpart; PL b/c roughly correspond to SIL 1, PL d to SIL 2 and PL e to SIL 3. These are order-of-magnitude comparisons, not a conversion formula – the input parameters, failure measures and decision paths differ, so you cannot swap one table for another. Subsystems from both standards may be combined in one machine, but each must be assessed and documented on its own.
In practice, European machine builders and CE export projects tend to use the PL language of ISO 13849-1, while process industry and some safety-PLC datasheets quote SIL. On an export project, ask which language the customer or machine standard requires before choosing which method to calculate and document.
40.9 Architecture quick reference – continue from the wiring article
| Architecture | Typical achievable | Bypass resistance | Diagnostic coverage | Wiring complexity | Cost |
|---|---|---|---|---|---|
| Dedicated safety relay | PL d / e (depends on model) | Medium | Medium to high (EDM readback) | Medium | Low to medium |
| Safety PLC (PROFIsafe / CIP Safety / Safety over EtherCAT) | PL e / SIL 3 | High | High | Medium (bus plus parameterisation) | High |
| Ordinary PLC output used for safety | Not recommended for a high PL claim | Low | Low | Low | Low |
| Mixed (safety relay plus safety PLC) | up to PL e | High | High | High | High |
For the actual STO/SS1 wiring, dual channels and EDM readback of each architecture, see Machine safety circuits: STO vs SS1, stop categories, dual channels and EDM; for the Fanuc emergency-stop signal chain see Fanuc emergency stop circuit; for a Heidenhain guard interlock chain see Heidenhain guard doors open alarm; for Siemens Safety Integrated alarms see 840D sl Safety Integrated alarms.
40.10 Verification and records: functional tests, single-fault injection, EDM readback
Calculating a PL is not the end – the function must be verified and recorded:
- Functional tests: emergency stop, guard door, light curtain and STO drop-out – test each for trigger, stop, no automatic restart, and recovery only by the prescribed reset.
- Single-fault injection: on each channel, open one wire, short to 24 V, and simulate a stuck contact; verify that a single fault does not lose the safety function and is detected or annunciated.
- EDM readback: confirm that the actual contactor state matches the command and that the reset circuit cannot bypass it.
Suggested record-sheet fields (copy into your test procedure as a starting point):
| ID | Safety function | PLr | measured PL | Trigger device | Stop time | Single-fault injection result | EDM readback | Verdict | Tester/date |
|---|---|---|---|---|---|---|---|---|---|
| F01 | Emergency stop | d | d | E-stop button | fill in measured | open/stuck, each item | OK / fault | pass / fix | fill in |
| F02 | Guard interlock | d | d | Guard switch | fill in measured | open/short, each item | OK / fault | pass / fix | fill in |
| F03 | Light curtain | d | – | OSSD | fill in measured | blocking/short, each item | OK / fault | pass / fix | fill in |
| F04 | STO drop-out | d | – | Safety relay | fill in measured | channel 1/2 opened separately | OK / fault | pass / fix | fill in |
This is a sample template organised around the verification stage of ISO 13849-1; adapt fields and acceptance thresholds to your risk assessment and the standard edition in use.
40.11 Export-compliance view: what to prepare for the CE technical file
For CE export projects, the safety-related part of the file normally needs to show:
- The machine risk assessment and a list of safety functions, each with PLr and its justification.
- The PL calculation: architecture, MTTFd / DCavg / CCF values and their sources (B10d, T10d and diagnostic-coverage data from component datasheets).
- The CCF scoring sheet (Annex F, item by item, at least 65 points).
- Verification records (the test table above) and the maintenance plan (replace at T10d).
- Manufacturer declarations of conformity and datasheet pages for safety-related components.
This article gives a method framework and band-level lookup only, not legal or certification advice; formal projects must follow the original text of the adopted standard edition and the requirements of your notified body or customer.
Frequently Asked Questions
What is the difference between PL and PLr, and does a PL e safety relay make the machine PL e?
PL is the level a safety function actually achieves, calculated from architecture and component data; PLr is the level required by the risk assessment, derived from the S/F/P risk graph; the acceptance condition is PL >= PLr. PL belongs to the whole sensor-to-logic-to-output chain, not to one component: if the guard switch or output contactor has only low-band MTTFd/DC, the chain cannot reach PL e even when the relay is rated PL e.
What PL can a Category 3 dual-channel circuit reach, and why?
On the simplified PL chart, Category 3 with low DCavg gives PL b/c/d depending on MTTFd, and Category 3 with medium DCavg gives PL c/d/d – so in the simplified table Category 3 is normally capped at d, and PL e goes through Category 4 or a full PFH_D calculation. The reason is that dual channels only guarantee that a single fault does not lose the function; accumulated undetected faults can still do so, and DCavg plus MTTFd determine which band it lands in.
Does an emergency stop need dual channels, and how do I choose stop category 0 or 1?
Whether dual channels are needed follows the PLr of that particular emergency-stop function: PLr d/e normally needs dual-channel redundancy with diagnostics, while a low PLr can use a single channel. As for Cat 0 / Cat 1, note that these are stop categories from IEC 60204-1, a completely different classification from the ISO 13849-1 architecture Categories B/1/2/3/4 – do not mix them. Cat 0 removes power to the actuators immediately (uncontrolled stop); Cat 1 makes a controlled decelerating stop and removes power only once stopped. Choose Cat 1 where inertia or process needs a controlled stop and Cat 0 where the hazardous motion must be removed immediately, per the risk assessment and the machine standard.
Last updated: 2026-11-24
Where to go next
- FANUC Troubleshooting — the full guide library: alarms, diagnosis numbers, servo, spindle, PMC and electrical faults, organised by symptom.
- CNC Repair Tools — which instrument measures what: multimeters, clamp meters, insulation testers and oscilloscopes, with the specification that actually matters.
- Remote Technical Support — have the readings reviewed with you: alarm reverse lookup, PMC ladder analysis and servo tuning advice by call. Repair companies and integrators welcome.
- Buying & Ownership Decisions — refurbished vs new, used-machine checks, software licensing and manuals: spend with the field facts in hand.