Evidence level first. The root-cause conclusion below comes from a publicly documented field case that another user independently reproduced, cross-checked against alarm references. Numbers such as 1Ω / 5Ω, .030″ / .050″ gaps and torque values are field-case reference figures, not official FANUC parameters. Verify every parameter number and threshold against the manual shipped with your machine and the builder’s process sheet. This site does not host manuals, cracks or part-sales links.
45.1 Start with the machine class, not the generic alarm table
Wire EDM, sinker EDM and travelling-wire machines share three traits:
- Dedicated alarm ranges that do not map one-to-one onto general PS/SV lists.
- Short-circuit detection, inter-electrode gap and flushing controlled by the EDM side; PMC and servo only execute.
- Ground reference is part of the process, not an optional convenience.
So reverse the usual order: check the EDM-side state first (short indicator, flushing, gap, ground path), then look at CNC/servo alarms. Opening a general alarm table first already points you the wrong way.
45.2 A-1ic versus A-0ib: sensitivity, not a software version
The field consensus is that A-1ic short-circuit detection is more sensitive and demands a better ground path. That explains why the same R1 technology runs on an A-0ib but throws a reverse alarm on an A-1ic.
| Item | A-0ib (field case) | A-1ic (field case) |
|---|---|---|
| Short-circuit sensitivity | Lower | Higher |
| Ground resistance reference | under 5Ω acceptable | under 1Ω required |
| Detection approach | voltage threshold | current-sensing loop |
These numbers come from a single field-case article. Use them to decide whether grounding is *obviously* bad, never as a factory spec. The portable conclusion is one sentence: A-1ic is far less tolerant of a floating or high-resistance ground, so the same wiring defect can be silent on an A-0ib and fatal on an A-1ic.
One parameter correction matters here. That widely circulated article describes parameter 1815 as a “motor overload level 0-200%” and lists 1820/1825/2003 values. This conflicts with the standard FANUC use of 1815 for absolute-position detector and reference-point setup (for example 1815#4 APZ). We do not repeat that claim. See homing failure classification for the reference-point side of this family, and verify all parameter numbers in your own manual.
45.3 Reverse alarm root cause: false short detection, not cutter comp
The classic field pattern is:
- R1 technology throws Reverse Alarm at path reversal;
- the short icon stays off, and the wire visibly clears the steel;
- the same program runs fine on an A-0ib.
When all three hold, a real short and an oversized cutter compensation are both unlikely. Oversized comp normally produces an interference or path alarm, not a reverse trip with no short indication.
In a documented case, the final root cause was the red ground wire posted to the wrong point on the lower head after a rebuild. The floating reference made the short-detection circuit misread the reversal transient as a polarity fault. Another user replied that he had made the same mistake with “that one red ground wire” – a reproducible field clue, not theory.
Rule of thumb: reverse alarm + no short icon = check ground and wiring first. Do not touch cutter comp or feed parameters yet.

45.4 Four field checks: from terminal to gap
Do these in order; most “ghost” alarms reveal themselves in the first three steps:
- Inspect the ground terminal. Look for corrosion, looseness, or insulation trapped under the lug. In the cited case the wire was connected to the wrong point, not broken.
- Dedicated lug directly to the cast-iron head. Metal-to-metal contact is required; a plastic housing or coated surface does not count. Photograph routing before disassembly and use a torque tool on reassembly.
- Measure continuity with a milliohmmeter. From the lower head to the power-supply chassis ground bus. The case used “under 1Ω” as a rebuild check – a field reference, not an official spec.
- Check flushing fluid, pressure and inter-electrode gap. Insufficient flushing can create a momentary short even when the static gap is adequate. The case cites .030″ (0.76 mm) static and .050″ (1.27 mm) dynamic gaps as process references; follow your own process sheet.
After reassembly, run the exact R1 program that failed. Confirm the short icon stays off through the reversal, servo load is smooth, and the alarm does not return. A reset that “fixes” it does not count – you must complete a full reversal sequence.

45.5 Emergency workaround: A1 technology works with a cost
If the ground cannot be repaired immediately, switching R1 to A1 technology can keep production moving. A1 uses a different feed algorithm that is less sensitive to ground reference; the case author finished his clearance cuts this way.
Be explicit about the cost: A1 gives poorer corner control. It suits clearance, non-critical corner relief and slug separation, not precision die cavities. It is a bridge to shipment, not a repair conclusion. The ground still needs fixing or R1 will fail again.
45.6 Alarm 317: treat it as low APC battery first
Sources agree on the core meaning: 317/327/337… means the APC (absolute pulse coder) battery for axis n has fallen to a level requiring replacement. In “317 X ABS. Pulse Coder”, X is the reporting axis. This is not a blanket encoder communication fault, and it is not a reason to replace the servo amplifier first.
Likely causes, in field order:
| Cause | Action |
|---|---|
| APC backup battery exhausted | Replace battery, then re-establish the reference per procedure |
| Reference not set after battery change | Perform reference return and rebuild absolute zero |
| Signal-line noise, open wire, contaminated connector | Check encoder cable and plug, especially in coolant areas |
| APC interface board ageing (electrolytics etc.) | Board-level test or exchange |
| Main / memory subsystem fault | Check parameter and SRAM backup, diagnostics and board state |
Decisive test: if 317 clears after a battery change or reference return but returns at the next power-on, this is no longer a one-off lost-position event. Chase hardware: encoder cable and connector ingress, APC board capacitors, then the main board. Stop cycling power.
Also separate two battery families: 306/307 is the CNC parameter/memory backup battery, while 317 is the APC absolute-position battery. The replacement procedures and data-loss risks differ. See FANUC battery alarms 306/307 and APC and homing failures: reference not found vs wrong reference.

45.7 317 plus black screen and a red board LED: look at the main board
When 317 arrives with the following symptoms, the encoder is probably not the primary fault:
- 317 appears on first power-up after a machine move or long idle period;
- the LCD shows fragmented graphics, especially after a CRT-to-LCD retrofit;
- the keyboard responds intermittently;
- a red LED is lit next to the green power-good LED on the main board.
On FANUC 0 / 0i main boards, that red LED commonly indicates CPU halt, watchdog timeout, or memory parity/refresh error. Together with a fragmented display and an unreadable absolute position, the picture points to the main board or memory subsystem; 317 is the secondary symptom.
Order of work: confirm 24 V supply -> check parameter/SRAM backup integrity -> note exactly when the red LED lights (at power-on or later) -> only then decide between APC board, interface board and main board. For board-number reading see A16B / A17B / A20B board families. Do not swap an encoder or amplifier just because 317 is on the screen.

45.8 Special-machine alarm family: do not copy the generic SV table
Wire EDM and sinker machines do show SV, SR and DS alarms, but the trigger conditions differ from general machines: EDM-side short detection, discharge state and flushing pressure often alarm before the servo itself. Only three things are firm in the field:
- full CNC alarm text including prefix and axis;
- the amplifier’s own 7-segment display;
- the special-machine diagnostic page and short/flushing status indicators.
Public “EDM alarm cross-reference” lists are mostly single-source commercial material; this page does not reproduce them as a code table. The *method* for grounding-related SV0381-family faults is in poor grounding and the external detector alarm family, and chain dropout method is in I/O Link & PROFIBUS station dropout. Those are methods, not EDM code tables.
45.9 Grounding is not optional
Industrial EDM requires a solid ground because discharge current uses the machine structure as a reference. A poor reference affects process stability, short-detection accuracy and personal safety at the same time. Two disciplines apply:
- Apply lockout/tagout before touching the lower head wiring and let drive capacitors discharge.
- Make the ground path measurable and traceable: lower-head lug -> dedicated ground wire -> supply chassis ground bus, verified end to end with a milliohmmeter and recorded after reassembly.
Many “parameter faults” and “process faults” turn out to be a ground wire resting on insulation. That is the lasting lesson of the A-1ic case.
45.10 Scope
This page provides no manual PDFs, no cracked material and no part-sales links, and does not treat a third-party list as a complete code table. The 1Ω/5Ω figures, gap values and torque figures from field cases are direction indicators only; parameters and thresholds come from your manual and process sheet. Special-machine documentation is scarce, which is exactly why you need hard evidence: full screen text, the amplifier’s raw display and a measured ground path.
Frequently Asked Questions
Is a wire EDM reverse alarm a cutter-comp problem or a grounding problem?
Check the short icon. If it is off, the wire visibly clears the steel, and the same program runs on a less sensitive model such as the A-0ib, a real short and oversized cutter comp are both unlikely. In the documented A-1ic case, the red ground wire was posted to the wrong point on the lower head after a rebuild; the floating reference made short detection misread the reversal. Check terminal contact and continuity first, not cutter comp or feed parameters.
Alarm 317 cleared, but it comes back at the next power-on. What does that mean?
It is no longer a one-off lost-position event. 317 means the axis n APC battery voltage has dropped to replacement level; after a battery change and reference return it should stay cleared. If it returns at the next power-on, check encoder cable and connector ingress, APC interface board capacitors, then the main or memory subsystem. If you also see a fragmented display, dead keyboard or a red board LED, prioritise the main board.
A-0ib runs fine while A-1ic throws a reverse alarm. Software or hardware difference?
Not simply a software version. The accepted difference is that A-1ic short detection is more sensitive and needs a much better ground; the same high-resistance ground can be silent on an A-0ib and false-trigger on an A-1ic. The cited 1Ω and 5Ω figures are field references, not factory specs. Repair the ground and wiring; A1 technology can bridge production but has poorer corner accuracy and is not suitable for precision die work.
Last updated: 2026-11-25
Where to go next
- FANUC Troubleshooting — the full guide library: alarms, diagnosis numbers, servo, spindle, PMC and electrical faults, organised by symptom.
- CNC Repair Tools — which instrument measures what: multimeters, clamp meters, insulation testers and oscilloscopes, with the specification that actually matters.
- Remote Technical Support — have the readings reviewed with you: alarm reverse lookup, PMC ladder analysis and servo tuning advice by call. Repair companies and integrators welcome.
- Buying & Ownership Decisions — refurbished vs new, used-machine checks, software licensing and manuals: spend with the field facts in hand.
Read the guide, get the right instrument, or walk the diagnosis through with someone — pick whichever you need.
The original Chinese version — same procedure, with the full field notes.












































暂无评论内容