60.1 Alarm prefixes SV / PS / MC: the same digits mean different things in each segment
The prefix before a FANUC alarm number tells you which subsystem it belongs to. The same digits under a different prefix mean something entirely different – identify the segment first, then the number.
| Prefix | Subsystem | Typical content | The two codes here |
|---|---|---|---|
| SV | Servo | Axes, amplifiers, encoders, sync control | SV0005 sync-axis error |
| PS / P/S | Program / System | Program format, parameter validity, setting conflicts | 5046 straightness-compensation parameter error |
| MC | Machine | Machine-builder PMC alarms | Defined by the builder, check their manual |
Table 60-1 SV / PS / MC segments and the alarms covered here
🔴 5046 has no SV prefix: it is a 5xxx P/S alarm, essentially a “parameter data failed validation” error, not a motor, drive or feedback hardware fault. Read the segment wrong and the whole diagnosis starts in the wrong direction.

60.2 SV0005 SYNC EXCESS ERROR (MCN): MCN means a real machine-coordinate divergence
The official message for SV0005 is SYNC EXCESS ERROR (MCN). In feed-axis synchronous control, a master and a slave axis run as a pair; the control continuously compares their machine coordinates. When the difference exceeds the sync-error tolerance parameter (No.8314), the alarm is raised – it can occur on either the master or the slave axis.
| Item | Content |
|---|---|
| Alarm / message | SV0005 (sometimes shown as 005) · SYNC EXCESS ERROR (MCN) |
| Trigger | Master/slave machine-coordinate difference > No.8314 setting |
| MCN meaning | Machine Coordinate – divergence detected on the machine-coordinate side |
| Nature | A real positional difference, not a command or calculation problem |
| Applies to | 0i-D / 0i-F / 30i-B and other series with sync control |
Table 60-2 SV0005 quick-reference card
🔴 The three letters MCN matter: the control is comparing the two axes’ actual mechanical positions, not command values and not calculated following error. SV0005 therefore does not appear out of nowhere from a “wrong calculation” – one axis really has fallen behind, or the tolerance is set unrealistically. See the Fanuc Alarm, Parameter and Diagnostic Cross-Reference Table for the sync-tolerance parameter system.
60.3 Six root causes of SV0005, ranked
Ordered by how often they occur in the field. The first, slave-axis mechanical binding, is the most common cause on a machine that has run correctly for years.
| # | Root cause | Typical clue |
|---|---|---|
| 1 | Slave axis mechanically binding / overloaded | Tight guide, worn ball screw, heavy load – the slave lags the master |
| 2 | Sync tolerance (No.8314) set too tight | Tolerance below the pair's normal following error – alarms on every move, often after a recent parameter change |
| 3 | Encoder / feedback fault on one axis | Dirty scale, loose feedback connector, failing encoder gives a false position |
| 4 | Slave drive / amplifier problem | Cannot deliver current, or that axis's breaker has tripped |
| 5 | Mechanical coupling loose or damaged | Slipping coupling, sheared key, loose clamp lets the axes separate under load |
| 6 | Not re-referenced after a crash or power-off move | The pair's relationship is lost, then sync mode is started anyway |
Table 60-3 Six root causes of SV0005 and their field clues

60.4 SV0005 diagnosis and clearing: re-reference after RESET
Recommended order: record first, then low-speed trial, then push-by-hand with power off, then electrical and parameters. Any work inside the cabinet, on live equipment or inside the drive must be done by qualified personnel following lock-out / tag-out (LOTO) procedures.
- Record first: note the exact alarm text and which axis pair is named; write down both machine coordinates before powering down.
- Handwheel low-speed trial: switch to handwheel / low-feed jog, move the pair a small amount, and see whether the alarm returns immediately or only under load.
- Push each axis by hand with drives off: compare resistance; a stiff axis points to a mechanical bind.
- Inspect the mechanical link: check couplings, keys and clamps between master and slave for movement or damage.
- Check the feedback loop: both axes’ feedback cables and connectors for damage, coolant ingress or loose plugs.
- Check the slave amplifier: its status and any accompanying alarms, and whether the breaker has tripped.
- Review the sync tolerance: compare No.8314 against the builder’s setting and check whether it was changed recently.
Clearing: fix the root cause first, then press RESET. If the pair has lost its relationship (crash or power-off move), re-reference / re-synchronise per the machine builder’s manual before production; a power cycle is only needed if the drive itself has latched a fault. One official recovery approach is: set SYNCx / SYNCJx (x = slave axis number) to 0 for normal running → temporarily increase No.8314 → clear with RESET → use the handwheel to bring the two machine coordinates close together → restore No.8314 to its original value. This is only a way to re-establish alignment, not a permanent fix by enlarging the tolerance.
60.5 Alarm 5046 ILLEGAL PARAMETER (ST.COMP): a parameter-validity error, not a mechanical fault
The official message for 5046 is ILLEGAL PARAMETER (ST.COMP); ST.COMP is straightness compensation. Straightness compensation lets the control bend the commanded path to correct an axis that does not travel perfectly straight. The control reads this data at power-up and whenever settings change; if validation fails it raises 5046 and refuses to run the axis.
| Aspect | SV0005 | 5046 |
|---|---|---|
| Alarm segment | Servo (SV) | Program/Format (P/S, 5xxx) |
| Nature | Real divergence of two axes' mechanical positions | Invalid straightness-compensation parameter data |
| Typical timing | During synchronous motion | After editing parameters, restoring a backup, loading from another machine |
| Clears with RESET? | Yes, once the cause is fixed | No – correct parameters and power-cycle to rebuild the table |
| Hardware-related | Possibly (axis / feedback / drive) | Usually not a hardware fault |
Table 60-4 SV0005 vs 5046 by segment (no causal link)
🔴 RESET does not clear 5046: the data itself is invalid. Correct the parameters and power-cycle so the table is rebuilt; the alarm disappears at power-up once validation passes.
60.6 Five official root causes of 5046
These five come from the FANUC operator’s-manual alarm lists (16i/18i/21i-B: B-63864EN/03; 21i-MB: B-63614EN/01; 16i/18i: B-63124EN/01). They are the manufacturer’s listed causes, not a forum paraphrase.
| # | Official cause (summarised from the manuals) |
|---|---|
| 1 | The axis number specified for the movement axis or compensation axis has no corresponding axis |
| 2 | Pitch-error compensation point numbering between the negative and positive ends is wrong / the point count exceeds the limit (wording varies slightly by manual edition) |
| 3 | Straightness compensation point numbers are not assigned in the correct order |
| 4 | A specified straightness compensation point lies outside the range between the positive-end and negative-end pitch-error compensation points |
| 5 | The compensation value at a point is too large or too small |
Table 60-5 Five official possible causes of alarm 5046
The most common field trigger is loading parameters or a backup from another machine or another control version, so point count, spacing or axis numbers no longer match. The first diagnostic step is always to compare against this machine’s own parameter list or known-good backup – never fill in values from a “generic” table found online.

60.7 Straightness compensation parameter checklist: points / spacing / start / end / direction / counting
When 5046 appears after a parameter change, verify these six items one by one. Check each against your machine’s manual and a known-good backup, not from memory.
| Item | What to check |
|---|---|
| Point count | Whether the number of pitch-error compensation points on the moving axis is within limits (interpolated-type straightness compensation requires no more than 128 points) |
| Spacing | Compensation point interval matches stored pitch-error compensation (taken from No.3624) |
| Start / end | End points lie between the positive/negative-end pitch points, direction agrees with axis travel |
| Order | Point numbers assigned sequentially with no gaps |
| Axis number | The axis numbers for movement and compensation axes exist on this machine |
| Compensation value | Each point's value is within the valid range (an over-limit value gives alarm 5321 S-COMP VALUE OVERFLOW) |
Table 60-6 Six-item straightness compensation parameter checklist
⚠️ After setting straightness compensation parameters the control normally shows P/S000 “PLEASE TURN OFF POWER” – you must power off and back on to rebuild the table. For related parameter systems see the Fanuc Pitch Error Compensation 3620-3624 guide and the Fanuc Backlash Compensation 1851 guide; always follow the machine’s own manual for the actual operation.
60.8 Cross-reference: 5046 versus straightness compensation parameter ranges by generation
This is the easiest section to get wrong: parameter numbers for straightness compensation differ across generations and models (Model A / Model B). The ranges below are traceable to official sources and serve only as cross-reference clues – always confirm against your machine’s manual before acting.
| Parameter range | Official meaning | Note |
|---|---|---|
| No.3624 | Pitch-error compensation point interval | Straightness compensation point interval is the same as pitch compensation |
| No.3605 #0 (IST) | Interpolated-type straightness compensation selection | 0 not used / 1 used |
| No.13391-13396 | Straightness compensation magnification for moving axes 1-6 | 0-100; 0 means no compensation, 1 means same unit as detection |
| No.13386 | Straightness compensation point number at the extremely negative point | Model A, word type, range 6000-6767 |
| No.13881-13886 | Straightness compensation settings | Model B; incorrect settings trigger 5046 |
| No.5700 (SMT / ST6) | Magnification application for multiple moving axes / combination count | ST6: 3 or 6 combinations |
| Alarm 5321 | S-COMP VALUE OVERFLOW | Compensation value over 32767, requires manual reference return |
Table 60-7 Straightness compensation parameter ranges (check by model)
🔴 Do not take this table to the shop floor as-is: Model A uses 13386 / 13391-13396, Model B uses 13881-13886, and 0i-B/C versus 16i/18i/21i place the functions in different ranges. Applying one model’s numbers to another is itself a common human cause of 5046.

60.9 Relationship to the alarm cross-reference table
The Fanuc Alarm, Parameter and Diagnostic Cross-Reference Table covers verified anchors across the SV / PS / OH segments, but SV0005 and 5046 have no standalone entries there. These two sections act as a dedicated supplement: SV0005 → segment SV → parameter 8314 → machine-coordinate divergence; 5046 → segment P/S → straightness compensation parameter ranges → parameter validation. The relationship between servo alarm numbers, amplifier seven-segment codes and diagnostic numbers is covered in the servo alarm cross-reference material.
One line to remember: identify the segment first (SV / PS / MC), then follow that segment’s own path; SV0005 means mechanical and sync checks, 5046 means parameters and backup source – keep the two lines separate.
Frequently Asked Questions
What is the difference between SV0005 and SV0405, and which side do I check first for a sync-axis alarm?
SV0005 is a master/slave machine-coordinate divergence (SYNC EXCESS ERROR (MCN), parameter 8314) – it looks at the actual position difference between the two axes. SV0405 is a Zero Point Return Fault, a position-control-system problem during reference-position return, and is not a sync-axis code. So check reference return for SV0405, and follow this article’s sync checks for SV0005.
Is alarm 5046 simply “the straightness compensation table is written wrong”?
Essentially yes. 5046 means the straightness compensation parameters failed the control’s validity check – common causes are invalid axis numbers, wrong point numbering or order, points outside the pitch-compensation range, values too large or small, or a backup loaded from another machine. RESET will not clear it; correct the parameters and power-cycle to rebuild the table.
Can I “solve” an over-limit sync position deviation by changing the sync tolerance parameter?
Not as a fix. Enlarging No.8314 is only for temporarily restoring the pair’s relationship (combined with bringing the two machine coordinates together), and must be restored to its original value afterwards. Leaving it enlarged hides real mechanical binding, loose couplings or feedback faults, which then return in a more serious form under heavier load.
Last updated: 2026-11-26
Where to go next
- FANUC Troubleshooting — the full guide library: alarms, diagnosis numbers, servo, spindle, PMC and electrical faults, organised by symptom.
- CNC Repair Tools — which instrument measures what: multimeters, clamp meters, insulation testers and oscilloscopes, with the specification that actually matters.
- Remote Technical Support — have the readings reviewed with you: alarm reverse lookup, PMC ladder analysis and servo tuning advice by call. Repair companies and integrators welcome.
- Buying & Ownership Decisions — refurbished vs new, used-machine checks, software licensing and manuals: spend with the field facts in hand.
Read the guide, get the right instrument, or walk the diagnosis through with someone — pick whichever you need.