FANUC SV0005 Sync-Axis Error and Alarm 5046 Straightness Compensation: M/S/C Segment Diagnosis and Parameter Checklist

Separate the two codes first: SV0005 and 5046 belong to two different alarm segments and have no causal link. SV0005 is a servo-segment (SV) sync-axis mechanical-coordinate divergence; 5046 is a program/format-segment (P/S, 5xxx) straightness-compensation parameter error. They are searched together only because both involve multi-axis motion. With that clear, treat each on its own path. Note also that SV0405, often compared here, is a Zero Point Return Fault and has nothing to do with sync axes. Parameter numbers below are traceable to official sources, but the applicable range and settings must be checked against your machine's own manual – do not copy any table blindly.

60.1 Alarm prefixes SV / PS / MC: the same digits mean different things in each segment

The prefix before a FANUC alarm number tells you which subsystem it belongs to. The same digits under a different prefix mean something entirely different – identify the segment first, then the number.

PrefixSubsystemTypical contentThe two codes here
SVServoAxes, amplifiers, encoders, sync controlSV0005 sync-axis error
PS / P/SProgram / SystemProgram format, parameter validity, setting conflicts5046 straightness-compensation parameter error
MCMachineMachine-builder PMC alarmsDefined by the builder, check their manual
广告

Table 60-1 SV / PS / MC segments and the alarms covered here

🔴 5046 has no SV prefix: it is a 5xxx P/S alarm, essentially a “parameter data failed validation” error, not a motor, drive or feedback hardware fault. Read the segment wrong and the whole diagnosis starts in the wrong direction.

SV0005 and 5046 two-segment alarm landscape

60.2 SV0005 SYNC EXCESS ERROR (MCN): MCN means a real machine-coordinate divergence

The official message for SV0005 is SYNC EXCESS ERROR (MCN). In feed-axis synchronous control, a master and a slave axis run as a pair; the control continuously compares their machine coordinates. When the difference exceeds the sync-error tolerance parameter (No.8314), the alarm is raised – it can occur on either the master or the slave axis.

ItemContent
Alarm / messageSV0005 (sometimes shown as 005) · SYNC EXCESS ERROR (MCN)
TriggerMaster/slave machine-coordinate difference > No.8314 setting
MCN meaningMachine Coordinate – divergence detected on the machine-coordinate side
NatureA real positional difference, not a command or calculation problem
Applies to0i-D / 0i-F / 30i-B and other series with sync control

Table 60-2 SV0005 quick-reference card

🔴 The three letters MCN matter: the control is comparing the two axes’ actual mechanical positions, not command values and not calculated following error. SV0005 therefore does not appear out of nowhere from a “wrong calculation” – one axis really has fallen behind, or the tolerance is set unrealistically. See the Fanuc Alarm, Parameter and Diagnostic Cross-Reference Table for the sync-tolerance parameter system.

60.3 Six root causes of SV0005, ranked

Ordered by how often they occur in the field. The first, slave-axis mechanical binding, is the most common cause on a machine that has run correctly for years.

#Root causeTypical clue
1Slave axis mechanically binding / overloadedTight guide, worn ball screw, heavy load – the slave lags the master
2Sync tolerance (No.8314) set too tightTolerance below the pair's normal following error – alarms on every move, often after a recent parameter change
3Encoder / feedback fault on one axisDirty scale, loose feedback connector, failing encoder gives a false position
4Slave drive / amplifier problemCannot deliver current, or that axis's breaker has tripped
5Mechanical coupling loose or damagedSlipping coupling, sheared key, loose clamp lets the axes separate under load
6Not re-referenced after a crash or power-off moveThe pair's relationship is lost, then sync mode is started anyway

Table 60-3 Six root causes of SV0005 and their field clues

Six root causes of SV0005

60.4 SV0005 diagnosis and clearing: re-reference after RESET

Recommended order: record first, then low-speed trial, then push-by-hand with power off, then electrical and parameters. Any work inside the cabinet, on live equipment or inside the drive must be done by qualified personnel following lock-out / tag-out (LOTO) procedures.

  1. Record first: note the exact alarm text and which axis pair is named; write down both machine coordinates before powering down.
  2. Handwheel low-speed trial: switch to handwheel / low-feed jog, move the pair a small amount, and see whether the alarm returns immediately or only under load.
  3. Push each axis by hand with drives off: compare resistance; a stiff axis points to a mechanical bind.
  4. Inspect the mechanical link: check couplings, keys and clamps between master and slave for movement or damage.
  5. Check the feedback loop: both axes’ feedback cables and connectors for damage, coolant ingress or loose plugs.
  6. Check the slave amplifier: its status and any accompanying alarms, and whether the breaker has tripped.
  7. Review the sync tolerance: compare No.8314 against the builder’s setting and check whether it was changed recently.

Clearing: fix the root cause first, then press RESET. If the pair has lost its relationship (crash or power-off move), re-reference / re-synchronise per the machine builder’s manual before production; a power cycle is only needed if the drive itself has latched a fault. One official recovery approach is: set SYNCx / SYNCJx (x = slave axis number) to 0 for normal running → temporarily increase No.8314 → clear with RESET → use the handwheel to bring the two machine coordinates close together → restore No.8314 to its original value. This is only a way to re-establish alignment, not a permanent fix by enlarging the tolerance.

60.5 Alarm 5046 ILLEGAL PARAMETER (ST.COMP): a parameter-validity error, not a mechanical fault

The official message for 5046 is ILLEGAL PARAMETER (ST.COMP); ST.COMP is straightness compensation. Straightness compensation lets the control bend the commanded path to correct an axis that does not travel perfectly straight. The control reads this data at power-up and whenever settings change; if validation fails it raises 5046 and refuses to run the axis.

AspectSV00055046
Alarm segmentServo (SV)Program/Format (P/S, 5xxx)
NatureReal divergence of two axes' mechanical positionsInvalid straightness-compensation parameter data
Typical timingDuring synchronous motionAfter editing parameters, restoring a backup, loading from another machine
Clears with RESET?Yes, once the cause is fixedNo – correct parameters and power-cycle to rebuild the table
Hardware-relatedPossibly (axis / feedback / drive)Usually not a hardware fault

Table 60-4 SV0005 vs 5046 by segment (no causal link)

🔴 RESET does not clear 5046: the data itself is invalid. Correct the parameters and power-cycle so the table is rebuilt; the alarm disappears at power-up once validation passes.

60.6 Five official root causes of 5046

These five come from the FANUC operator’s-manual alarm lists (16i/18i/21i-B: B-63864EN/03; 21i-MB: B-63614EN/01; 16i/18i: B-63124EN/01). They are the manufacturer’s listed causes, not a forum paraphrase.

#Official cause (summarised from the manuals)
1The axis number specified for the movement axis or compensation axis has no corresponding axis
2Pitch-error compensation point numbering between the negative and positive ends is wrong / the point count exceeds the limit (wording varies slightly by manual edition)
3Straightness compensation point numbers are not assigned in the correct order
4A specified straightness compensation point lies outside the range between the positive-end and negative-end pitch-error compensation points
5The compensation value at a point is too large or too small

Table 60-5 Five official possible causes of alarm 5046

The most common field trigger is loading parameters or a backup from another machine or another control version, so point count, spacing or axis numbers no longer match. The first diagnostic step is always to compare against this machine’s own parameter list or known-good backup – never fill in values from a “generic” table found online.

广告
Five causes of 5046 and parameter checklist

60.7 Straightness compensation parameter checklist: points / spacing / start / end / direction / counting

When 5046 appears after a parameter change, verify these six items one by one. Check each against your machine’s manual and a known-good backup, not from memory.

ItemWhat to check
Point countWhether the number of pitch-error compensation points on the moving axis is within limits (interpolated-type straightness compensation requires no more than 128 points)
SpacingCompensation point interval matches stored pitch-error compensation (taken from No.3624)
Start / endEnd points lie between the positive/negative-end pitch points, direction agrees with axis travel
OrderPoint numbers assigned sequentially with no gaps
Axis numberThe axis numbers for movement and compensation axes exist on this machine
Compensation valueEach point's value is within the valid range (an over-limit value gives alarm 5321 S-COMP VALUE OVERFLOW)

Table 60-6 Six-item straightness compensation parameter checklist

⚠️ After setting straightness compensation parameters the control normally shows P/S000 “PLEASE TURN OFF POWER” – you must power off and back on to rebuild the table. For related parameter systems see the Fanuc Pitch Error Compensation 3620-3624 guide and the Fanuc Backlash Compensation 1851 guide; always follow the machine’s own manual for the actual operation.

60.8 Cross-reference: 5046 versus straightness compensation parameter ranges by generation

This is the easiest section to get wrong: parameter numbers for straightness compensation differ across generations and models (Model A / Model B). The ranges below are traceable to official sources and serve only as cross-reference clues – always confirm against your machine’s manual before acting.

Parameter rangeOfficial meaningNote
No.3624Pitch-error compensation point intervalStraightness compensation point interval is the same as pitch compensation
No.3605 #0 (IST)Interpolated-type straightness compensation selection0 not used / 1 used
No.13391-13396Straightness compensation magnification for moving axes 1-60-100; 0 means no compensation, 1 means same unit as detection
No.13386Straightness compensation point number at the extremely negative pointModel A, word type, range 6000-6767
No.13881-13886Straightness compensation settingsModel B; incorrect settings trigger 5046
No.5700 (SMT / ST6)Magnification application for multiple moving axes / combination countST6: 3 or 6 combinations
Alarm 5321S-COMP VALUE OVERFLOWCompensation value over 32767, requires manual reference return

Table 60-7 Straightness compensation parameter ranges (check by model)

🔴 Do not take this table to the shop floor as-is: Model A uses 13386 / 13391-13396, Model B uses 13881-13886, and 0i-B/C versus 16i/18i/21i place the functions in different ranges. Applying one model’s numbers to another is itself a common human cause of 5046.

Parameter range differences by model

60.9 Relationship to the alarm cross-reference table

The Fanuc Alarm, Parameter and Diagnostic Cross-Reference Table covers verified anchors across the SV / PS / OH segments, but SV0005 and 5046 have no standalone entries there. These two sections act as a dedicated supplement: SV0005 → segment SV → parameter 8314 → machine-coordinate divergence; 5046 → segment P/S → straightness compensation parameter ranges → parameter validation. The relationship between servo alarm numbers, amplifier seven-segment codes and diagnostic numbers is covered in the servo alarm cross-reference material.

One line to remember: identify the segment first (SV / PS / MC), then follow that segment’s own path; SV0005 means mechanical and sync checks, 5046 means parameters and backup source – keep the two lines separate.

Frequently Asked Questions

What is the difference between SV0005 and SV0405, and which side do I check first for a sync-axis alarm?

SV0005 is a master/slave machine-coordinate divergence (SYNC EXCESS ERROR (MCN), parameter 8314) – it looks at the actual position difference between the two axes. SV0405 is a Zero Point Return Fault, a position-control-system problem during reference-position return, and is not a sync-axis code. So check reference return for SV0405, and follow this article’s sync checks for SV0005.

Is alarm 5046 simply “the straightness compensation table is written wrong”?

Essentially yes. 5046 means the straightness compensation parameters failed the control’s validity check – common causes are invalid axis numbers, wrong point numbering or order, points outside the pitch-compensation range, values too large or small, or a backup loaded from another machine. RESET will not clear it; correct the parameters and power-cycle to rebuild the table.

Can I “solve” an over-limit sync position deviation by changing the sync tolerance parameter?

Not as a fix. Enlarging No.8314 is only for temporarily restoring the pair’s relationship (combined with bringing the two machine coordinates together), and must be restored to its original value afterwards. Leaving it enlarged hides real mechanical binding, loose couplings or feedback faults, which then return in a more serious form under heavier load.

Last updated: 2026-11-26

Where to go next

Read the guide, get the right instrument, or walk the diagnosis through with someone — pick whichever you need.

Also available in Chinese: FANUC SV0005 同步轴误差与 5046 直线度补偿怎么查?M/S/C 段判定 + 参数自检清单
The original Chinese version — same procedure, with the full field notes.
© 版权声明
THE END
喜欢就支持一下吧
点赞15赞赏 分享
评论 抢沙发

请登录后发表评论

    暂无评论内容

CNC电气调试问题解答 | 数控机床电气工程师资料共享屋
CNC电气调试问题解答 | 数控机床电气工程师资料共享屋
CNC电气调试问题解答 | 数控机床电气工程师资料共享屋
CNC电气调试问题解答 | 数控机床电气工程师资料共享屋
CNC电气调试问题解答 | 数控机床电气工程师资料共享屋
CNC电气调试问题解答 | 数控机床电气工程师资料共享屋
图片-CNCShare | 数控电气技术中心
图片-CNCShare | 数控电气技术中心
图片-CNCShare | 数控电气技术中心
图片-CNCShare | 数控电气技术中心
图片-CNCShare | 数控电气技术中心
图片-CNCShare | 数控电气技术中心
FANUC SV0005 Sync-Axis Error and Alarm 5046 Straightness Compensation: M/S/C Segment Diagnosis and Parameter Checklist-CNCShare | 数控电气技术中心
FANUC SV0005 同步轴误差与 5046 直线度补偿怎么查?M/S/C 段判定 + 参数自检清单-CNCShare | 数控电气技术中心
FANUC Tool Nose Orientation T0–T9: Imaginary Tool-Tip Direction, 45° Chamfer Error and the Root Cause of Taper Oversize-CNCShare | 数控电气技术中心
FANUC 刀尖方位号 T0–T9 怎么定?假想刀尖方向表 + 45° 倒角残留误差算例 + 锥面超差根因-CNCShare | 数控电气技术中心
CNC Machine Accuracy Preservation: Preventive Maintenance Checklist — Daily / Weekly / Monthly / Quarterly / Semiannual / Annual Cycles with Items, Criteria and Printable Record Sheet-CNCShare | 数控电气技术中心
数控机床精度保持怎么做?预防性维护点检清单:日/周/月/季/半年/年度六级周期 × 检测项目 × 判据 × 记录表(可打印)-CNCShare | 数控电气技术中心
FANUC PMC / Siemens S7 / Mitsubishi FX Ladder Mnemonic and Address Cross-Brand Reference: Same Function, Three Notations + Address Map + Ladder Symbols-CNCShare | 数控电气技术中心
FANUC PMC / 西门子 S7 / 三菱 FX 梯形图助记符与地址类型跨品牌对照总表:同一功能三种写法 + 地址映射 + 梯形图符号对照-CNCShare | 数控电气技术中心
FANUC / SINUMERIK / Mitsubishi Macro and System Variable Cross-Brand Reference: Date, Tool Compensation, G54–G59, Common # Numbers-CNCShare | 数控电气技术中心
FANUC / 西门子 / 三菱 宏变量与系统变量跨品牌对照总表:日期时间 / 刀长刀补 / G54–G59 工件坐标 / 常用 # 号一次查全-CNCShare | 数控电气技术中心
Heidenhain TNC Safety Alarms: 126-xxxx Self-Test and Configuration, 1C7-xxxx MC Drives and SPLC, 230-0005 External Emergency Stop-CNCShare | 数控电气技术中心
海德汉 TNC 安全报警怎么查?126-xxxx 自检与安全配置 + 1C7-xxxx MC 驱动与 SPLC + 230-0005 外部急停(三族逐条对照)-CNCShare | 数控电气技术中心
文章精选
专心做好一件事
打造更优雅的WordPress主题-CNCShare | 数控电气技术中心
专心做好一件事
打造更优雅的WordPress主题