一句话答案:External (peripheral) FANUC alarms like EX1118 or AL2022 can be traced backward along a fixed path: alarm number → A address → ladder → I/O point, taking you from ‘no idea what this means’ to ‘which terminal do I measure.’ Two common traps are a missing DISPB instruction and number-only messages.
External (peripheral) alarms are the ones that stop a shop with no obvious way forward: the screen shows EX1118 or AL2022, the builder’s manual is long gone, and nobody answers the phone. There is a fixed reverse path though — alarm number → A address → ladder → I/O point — that takes you from “no idea what this means” to “which terminal do I measure”.
This guide walks that path down to the level of which soft key to press, and adds the two traps that actually cost people days: a ladder missing the DISPB function instruction (A address is on, but nothing is displayed) and what to do when the message only carries a number, with no I/O point.
1. First, Sort the Three Alarm Classes: System / Servo / Builder-Defined
Table 1 — Boundaries of the three alarm classes
| Class | Range | Who wrote it | In the FANUC manual? | Typical examples |
|---|---|---|---|---|
| System alarms | 900–976 | FANUC (CNC control-side hardware) | ✅ Yes | 900 ROM PARITY, 950 PMC, 974 F-BUS |
| Servo / spindle alarms | 4xx / 7xx | FANUC | ✅ Yes | 401 VRDY OFF, 749 serial spindle |
| Builder-defined (external) | 1000–2999 | The machine tool builder, written into the PMC | ❌ No — only in the machine's own documentation | EX1010, No1018, AL2022 |
What distinguishes external alarms:
- Numbered 1000–1999 or 2000–2999, usually prefixed
EX,No,ALorALM - Mechanically they are alarms the builder built on the PMC’s A address: set an A bit, match it with a message in the message screen, and it appears on the display
- What they monitor is always peripheral hardware: level switches, pressure switches, temperature switches, limit switches, magazine/turret position switches
One-line test: if you can look it up in a FANUC manual it is a system or servo alarm; if you cannot and it only exists in the machine’s documentation, it is a builder-defined external alarm. The distinction matters because the two take completely different routes — hardware diagnosis for the former, ladder reverse-lookup for the latter. System alarms (900–976) are covered in Fanuc System Alarm 900–976: Meaning and Board-Level Diagnosis.

2. Alarm Number ↔ A Address ↔ Message Text: Reading the Message Screen
Start with what the A address actually is. FANUC PMC addresses are X Y R K D T C A, and A is the alarm message address:
- A0 to A249 — 250 bytes, 8 bits each — 2000 message bits in total (which is where the “2000” in DISPB comes from, see Section 7)
- Each bit corresponds to one message. The builder sets an A bit in the ladder, and the system looks up the text registered for that address and displays it
⚠️ One common misconception has to be corrected here: the alarm number and the A address are not related by a fixed formula — the builder assigns them in the message screen. Seen in the field on identical logic: one machine has A0.0 → alarm 1000, another has A0.0 → alarm 2000; and there are assignments as irregular as A0.5 → 1036 and A1.0 → 1039. So do not try to compute “1000 + byte×8 + bit” — go to the message screen and read the actual correspondence.
Navigation:
- Put the machine in 【MDI】
- Press 【SYSTEM】
- Press the 【▶】 extension key 3 times
- Select 【PMC 配置】 → 【信息】(PMC configuration → Message)
Here you get the full alarm number → A address → symbol table, which is the index for everything that follows. A well-built machine writes the I/O point straight into the text (for example “EX1118 coolant tank low level (X14.0)”), so you can locate the fault at a glance. A poorly built one only carries the number — that is when you go to the four steps in Section 3.

3. Step 1 — PMC Maintenance → Signal Status: Which A Bit Is On?
First establish *which bit* is alarming.
Path: 【MDI】→【SYSTEM】→ 【▶】 ×3 →【PMC 维护】(PMC maintenance)→【信号状态】(Signal status)→ A address page
- The page lists the A addresses (e.g. A0.0) together with the symbol number in blue
- A bit showing 1 is the alarm currently being triggered (A0.0 = 1 is typically the emergency stop alarm)
- Several bits may be on at once — cross-check against the alarm number on screen and the message-screen table to find the primary cause, and do not get dragged along by consequential alarms
Tip: if the alarm flashes and clears before you can read it, sit on the signal-status page and trigger the action again. Very often this bit is only the *result* — the real condition is further back in the ladder.
4. Step 2 — Find the Coil in the Ladder and Work Backwards Through the Contacts
Once you have the A address (or the alarm number), go to the ladder and locate its coil.
Path: 【SYSTEM】→ 【▶】 ×3 →【PMC 梯图】(PMC ladder)
- Enter the search term: you can type the A address (e.g.
A0.0), or the alarm number (e.g.#1000) - Press the 【W-搜索】(W-search) soft key — the cursor jumps straight to the coil for that alarm
- Work backwards: look at the contacts in series *before* the coil — usually an input-signal contact (e.g. the normally-closed contact of X8.4)
The emergency-stop example is the classic one: normally the external E-stop switch is a normally-closed contact; once powered, PMC contact X8.4 (normally closed) opens and the A0.0 coil stays off. When you press E-stop or a wire breaks, X8.4 (normally closed) closes, A0.0 turns on → alarm. So for this one you check two things specifically: is the E-stop switch stuck, and is the wire broken or poorly connected.
Core rule for reverse lookup: the coil is the *result*; the contacts in series before it are the *cause*. Walk upward step by step until you reach the outermost physical input (an X point) or internal condition (R relay, timer, counter).
For ladder basics and live monitoring, see FANUC PMC Ladder: From Signal Addresses to Live Monitoring.
5. Step 3 — Map the X Bit Back to the Electrical Drawing and Terminal Strip
Finding the X point only gives you a *logical address*; you still have to land it on physical wiring.
- X point → I/O module: first see which I/O Link module that X address belongs to (open the PMC I/O module allocation screen to confirm group/rack/slot and the start address)
- Module → terminal strip: using the module’s wiring/address table, map Xm.n to the actual terminal number
- On-site measurement: at the terminal strip, measure continuity / voltage on that point — decide whether the switch is bad, the wire is broken, or the contact is oxidized
⚠️ The bit-drift trap: the X point written in the alarm text was hard-coded against the I/O Link allocation at the time. Once that allocation changes — add/remove a module, change the byte count (e.g. OC01I → OC02I), or reorder groups — every X address on the later modules shifts as a block. You then get the mismatch “the alarm says X14.0, but the real signal is at X20.0”. So always trust the current I/O allocation plus the ladder, not the point number frozen into old text.
6. Step 4 — Reverse Verification: Force the Input Manually, Does the Alarm Reproduce?
The first three steps *infer*; step 4 *verifies*. The only purpose: confirm the chain you found is really the cause, not a parallel branch beside it.
Method: under safe mechanical conditions (stop what you can, lock the axes you can), artificially create a state change on that input:
- Physical side: short / open the corresponding terminal, or manually toggle the switch / press the button
- PMC side: use PMC’s FORCE function to force that X bit to 1 / 0 (always release the force when done!)
Reading the result:
- Alarm appears / disappears as expected → chain confirmed, the fault is in that switch or that wire
- Alarm does not react → you looked in the wrong place: go back to step 2 and re-trace, watching for parallel conditions, a self-holding loop, or a double coil (when the same A address is driven in two places, it may not actually conduct)
- Alarm comes and goes → most likely poor contact, oxidized contact or a loose terminal — chase the connector, not the spare parts
Iron rule: always release the force when you are done. Forget, and the machine runs with a “fake” signal — the most dangerous kind of man-made hazard.

7. Trap 1 — A Address Is Already On, but Nothing Is Displayed? Probably Missing DISPB
This is the most maddening case: in PMC status monitoring you see A0.5 and A1.0 clearly triggered (=1), and their message text is filled in on the message screen (e.g. A0.5 → 1036), yet the screen shows no alarm at all.
Cause: the ladder is missing the message-display function instruction DISPB (SUB 41) — deleted or skipped by mistake while editing the program.
The full display chain is:
The ladder sets the A bit → DISPB tells the system → the system reads the message text for that A address → it is shown on the screen
Without DISPB in the chain, an on A address has nobody to notify the system, so naturally nothing is displayed.
How to set “info count” in DISPB: on a 0i-D, the A range is A0~A249 = 250 bytes × 8 bits = 2000 message bits, so you enter 2000 in the instruction. The A range differs between models — follow your machine’s PMC specification.
Two more reasons that also cause “triggered but not displayed” (check them together):
- Double coil: the same A address driven in two places, may not actually conduct
- Incomplete PMC program in a simulator / test environment (most common on a simulator)
8. Trap 2 — The Message Carries Only a Number, No I/O Point
Many machines’ messages are written bare — just a number like EX2022, no address, no symbol, no I/O point. Find it in this order:
① Search by A address first; if it is not found, search by the symbol name
Some builders do not use the A address directly, but implement it with an internal relay R plus a data-transfer instruction. Type A0.0 and you get “address/symbol not found”, because the coil is actually R0700.0 or similar, and the symbol name *is* that alarm number (maybe with a prefix: 2000 / EX2000 / AL2000 / No.2000). So type the alarm number itself (e.g. 2000) and press W-search — the cursor lands on that R coil.
② If the R coil has no symbol name either, search the data-transfer instructions
If the R coil has no symbol name, search the function instructions. Common transfer instructions:
Table 2 — Common PMC data-transfer function instructions
| Instruction | Meaning |
|---|---|
| SUB43 / MOVB | 1-byte data transfer |
| SUB44 / MOVW | 2-byte data transfer |
| SUB47 / MOVD | 4-byte data transfer |
| SUB45 / MOVN | arbitrary-byte data transfer |
| SUB8 / MOVE | logical-AND then transfer |
| SUB28 / MOVOR | logical-OR then transfer |
Search each of these in the PMC; the one whose source is R and destination is A is your target.
③ Compute back by byte correspondence
For example a SUB45/MOVN: byte count 30, source R0700~R0729, destination A000~A0029 — R and A correspond byte by byte. A5.0 is the 5th byte, so it maps to R0705.0 (R0700 is the start). Once you have the R, trace upward to its driving condition.
④ Whole-byte usage
Some builders use the A address by the whole byte: e.g. each bit of R580 turning on triggers A0.0~A0.7 respectively. Find that A byte, then find its R relationship.
The rule never changes: whether the builder writes A directly or wraps a layer of R plus transfer instruction, it ultimately lands on “which physical input drives it”. The detour only adds one more instruction search.

Frequently Asked Questions
My FANUC ladder shows the A address already energized — why no alarm?
The most common reason is the ladder is missing the message-display function instruction DISPB (SUB 41) — the display chain is “ladder sets A address → DISPB notifies the system → system reads the message text → display”; without DISPB nobody notifies the system, so an on A address still shows nothing. Add DISPB back (set “info count” to your machine’s total A-bit count; on 0i-D it is commonly 2000 = A0~A249, 250 bytes × 8 bits). Two secondary reasons: a double coil on the same A address (actually not conducting), and testing on a simulator (the PMC program itself is incomplete).
How do I tell a PMC alarm from a system alarm? Which class is number 1000?
Number 1000 is a builder-defined external (PMC) alarm, not a system alarm. System alarms are 900–976 (CNC control-side hardware faults, in the FANUC manual, and cannot be cleared with the reset key); servo/spindle are 4xx / 7xx; and the 1000–2999 range is alarms the builder wrote into the PMC, triggered via the A address — not in the FANUC manual, only in the machine’s documentation. The distinction matters for the route: system alarms go to hardware diagnosis, external alarms go to the reverse lookup “alarm number → A address → ladder → I/O point”.
How do I find the cause when the builder’s alarm manual is missing?
Run the four-step reverse lookup: ① 【MDI】→【SYSTEM】→ 【▶】 ×3 →【PMC 维护】→【信号状态】, find the A bit showing 1; ② in 【PMC 梯图】 type that A address (or alarm number) and press 【W-搜索】 to locate the coil, then trace back the contacts in series before it; ③ map the X point back to the module and terminal strip per the I/O Link allocation, watching for bit drift when the allocation has changed; ④ manually force or short that input to reverse-verify the alarm appears/disappears. If the message screen (【PMC 配置】→【信息】) shows the alarm-number → A-address → symbol table, use it as your index first.
Last updated: 2026-10-21
Further reading (EN): FANUC ATC Alarms 1010–1024 — Why They Are Not in the Fanuc Manual, and How to Trace Them — same external PMC alarm topic, but for the specific 1010–1024 band with the A-address mapping, a four-builder same-number-different-meaning comparison, and the nine-step tool-change field order.
Related (EN): How to use PMC force output: verifying a signal after you trace it to an I/O point — this page covers tracing external alarms (1000/2000 range) from A address to ladder to I/O point; once you reach the Y point, that one shows how to force it on/off to tell “bad valve, broken wire, or logic never arrived”. The two go together.
Related (EN): How to troubleshoot I/O Link & PROFIBUS station dropout: ER97, the chain rule, BF LEDs — this page traces an alarm down to a concrete I/O point; if every point on a module reads zero, the problem is usually the bus rather than the signal. That one covers the I/O Link chain rule, the three on-site checks and the PROFIBUS five checks – the step before this one.
Where to go next
- FANUC Troubleshooting — the full guide library: alarms, diagnosis numbers, servo, spindle, PMC and electrical faults, organised by symptom.
- CNC Repair Tools — which instrument measures what: multimeters, clamp meters, insulation testers and oscilloscopes, with the specification that actually matters.
- Remote Technical Support — have the readings reviewed with you: alarm reverse lookup, PMC ladder analysis and servo tuning advice by call. Repair companies and integrators welcome.
Read the guide, get the right instrument, or walk the diagnosis through with someone — pick whichever you need.
The original Chinese version — same procedure, with the full field notes.











































暂无评论内容